Kansas City |
Code of Ordinances |
Chapter 34. HEALTH AND SANITATION |
Article XVI. LODGING ESTABLISHMENTS |
Division 2. LODGING ESTABLISHMENT REQUIREMENTS |
§ 34-610. Electrical.
Installation and maintenance of electrical components shall be in compliance with local codes. General requirements are as follows:
(1)
New lodging establishments having electrical outlets installed within five feet of wet locations or outdoors are required to be fitted with ground-fault circuit interrupters. Existing lodging establishments undergoing a major renovation or rewiring shall be required to install ground-fault circuit interrupters in electrical outlets located within five feet of wet locations or outdoors;
(2)
Electrical switches, outlets and junction boxes must be covered and properly protected from physical damage at all times;
(3)
All appliances must be grounded to design specifications;
(4)
Wire splices shall be located in covered junction boxes at all times;
(5)
Bare or frayed wiring is prohibited;
(6)
Three-prong receptacles must be properly grounded at all times. Non-grounded three-prong receptacles in existing lodging establishments shall be replaced with two-prong receptacles or properly grounded;
(7)
Temporary wiring and flexible cords cannot be used in place of fixed wiring. Use of extension cords longer than six feet shall be prohibited unless provided with over-current protection or rated with properly sized wire. No more than two extension cords per room may be used;
(8)
Wattage of light bulbs shall not exceed the wattage rating of corresponding light fixtures;
(9)
Empty light sockets are prohibited;
(10)
Circuit boxes shall be protected from physical damage and maintained in good condition. Storage of items that obstruct the vision of or access to circuit boxes is prohibited; and
(11)
Access to electrical panels shall be unobstructed; fuses and circuits must be labeled for identification.
(Ord. No. 140032 , § 4, 1-23-14)